GARUN Process Engineering
Environment · 2026-10-15

HCl scrubbing: what the outlet limit actually requires

Environment2026-10-15GARUN engineering

Acid mist is the reason perfectly good scrubbing towers fail stack tests. The gas-phase hydrogen chloride is easy: water absorbs it readily, and a single packed bed with circulating dilute acid will take the concentration down by an order of magnitude. The mist is a different problem, and it is the one that produces the visible plume.

Three-stage FRP absorption tower for hydrogen chloride off-gas
Three-stage FRP absorption tower for hydrogen chloride off-gas

Two things are leaving the dryer

The vapour from a drum dryer carries hydrogen chloride in two forms: dissolved in the water vapour as a gas, and as sub-micron droplets of hydrochloric acid formed when the vapour cools in the duct. The first behaves like a gas and diffuses into the liquid film on the packing. The second behaves like a particle and follows the streamlines straight through the bed.

This is why a two-stage tower can measure well on a gas-phase instrument and produce a visible plume at the same time. The mass that fails the test is not the mass the packed bed was designed to remove.

What each stage is for

StageMechanismRemovesTypical outlet
Quench / pre-coolDirect contact with circulating liquid, gas cooled below 60 °CCoarse mist, heat load—
Packed absorptionGas dissolves into the liquid film on the packing surfaceGas-phase HCl50–150 mg/m³
Mist eliminationChevron or candle filter, inertial capture of dropletsSub-micron acid mist≤10 mg/m³
Alkali polish (optional)Caustic circulation on a second bedResidual gas and mist for tight limits≤5 mg/m³

Outlet figures assume design gas flow, a working demister wash and correct liquid distribution. Any one of those failing moves the number by an order of magnitude.

The four reasons a good tower fails

  1. 01

    The demister is blinded

    A chevron or candle element that is never washed accumulates salts and dust until the gas finds a path around it. It is the single most common failure and it is a maintenance issue, not a design one.

  2. 02

    The hoods leak

    A tower sized for 10,000 m³/h connected to hoods that admit 4,000 m³/h of room air is a tower running at 140% of design. Capture at the hood comes before treatment in the tower.

  3. 03

    The liquid distributor is unbalanced

    Half the packing runs dry and the effective bed height halves. A distributor with blocked holes looks fine from the platform.

  4. 04

    The fan was selected on the catalogue

    System resistance rises as the packing ages and the ductwork fouls. A fan with no margin delivers less flow, velocity drops, and capture at the hood fails.

Designing to a number

The design sequence we use is: count every hooded source, add 15% for leakage and future tie-ins, set the tower diameter on a superficial velocity of 1.2–1.8 m/s, size the packing for the inlet concentration and the outlet limit, then specify the demister and its wash system as a separate duty. The fan is selected last, on the whole system, with margin.

That order matters. When the tower is chosen from a table and the fan is chosen afterwards to fit the budget, the plant gets a tower that is slightly too small and a fan that is slightly too weak — and the stack test finds both.

Testing note: agree the test method with the authority before the plant starts. Some jurisdictions measure total HCl, some measure mist separately, some measure opacity. A tower designed for the wrong metric passes its own criterion and fails the permit.